■ Measurement: three-phase kWh, kvarh, U, I, P, Q, S, PF, F
■ Current input: 3 × 1(6)A, 3 × 10(80)A(direct)
■ Programmable keys, LCD Display
■ Communication: Max. 2 pcs of RS485 interface
■ Digital input/output
■ Temperature monitor: NTC sensors
■ Harmonic: 2~31st and total Harmonic
■ Measurement:
kWh(2 directions), kvarh(2 directions), kWh of every phase
U, I, P, Q, S, PF, F
■ Harmonic: 2~31st and total Harmonic
■ LCD Display, Back linght
■ HMI, programable buttons, Back linght
Code, Protocol, Address, Baud rate, Parity, CT/PT Ratio
■ Active energy pulse output
■ Digital input, Digital output
■ Alarms: Undervoltage, overvoltage
■ Temperature monitor: NTC sensors
■ Infrared communication
■ Max.2 pcs RS485 communication port(Modbus RTU)
■ Multi-rate/Flexible Tariff:
4 time zones, 4 tariff rate (Spike, Peak, Flat, Valley)
2 time periods list, 14 time periods in day
■ Data Function: Frozen Data(last 48 months or last 90 days),Max Demand
■ Din rail mounted meter
■ Connection types: 3 phases 4 wires, 3 phases 3 wires,
■ Input voltage: 3×57.7/100 V, 3×220/380 V, 3×100 V, 3×380 V
Frequency: 45~65Hz
Power consumption: < 10 VA(every phase)
■ Input current: 3 × 1(6)A, 3 × 10(80)A
3 × 1(6)A(provided with CTs)
3 × 10(100)A(provided with CTs)
Consumption: < 1 VA(every phase)
■ Temperature monitor: NTC sensors, for 3 circuits, -40℃~99℃
■ Accuracy:
kWh: 0.5S class
kvarh: 2.0 class
■ Digital input: quantity: 1
Digital output: quantity: 1
■ Range of measuring: 000000.00~99999999kWh
■ Active energy pulse:
Pulse width: 80±20ms
Pulse constant: 6400imp/kWh, 400imp/kWh
■ Communication: Interface RS485, Modbus RTU protocol, 1200bps~19200bps
■ Work Environment:
Work temperature: -25℃~55℃
Relative humidity: ≤95%(No condensation)
Altitude: <2000m
■ Basic model:
Provided without CT:
ADL3000-E/C
Provided with CT:
ADL3000-E/CT C
■ Optional function:(Place as your technical requirements)
Tariff: F
Digital input/output: K
Temperature monitor: T
Measurement harmonic: H
Second port: 2C
■ Selected model:
ADL3000-E/C K H