IEC 60364-7-710CE Certified
Patient safety · Continuity of care

Medical Isolated Power Supply Systems for Hospitals — Monitoring, fault detection & IEC standards

A medical IT system isolates the supply and monitors insulation in operating theatres, ICU and emergency areas — so faults are found before they interrupt care.

3.15–10 kVA
Isolating transformer (AITR)
1–999 kΩ
Insulation monitoring (AIM)
up to 48
Fault-location circuits (AIL)
1 fault
Supply never interrupted

Why a medical IT system

Group 2 medical locations — continuity is a patient-safety matter.

A medical IT system is an unearthed distribution arrangement used in designated medical locations, combining an isolating transformer with insulation monitoring to keep power running after a first insulation fault and to limit leakage and touch current.

No interruption on first fault

Power stays on after an insulation fault; staff fix it on a planned schedule.

Leakage current limited

The isolating transformer keeps leakage and touch current within safe limits.

Fault found early

Monitoring + fault locator pinpoints the branch, so teams act on evidence.

System architecture

One continuous system, transformer to nurse station.
Acrel medical IT system architecture — cloud, gateway and IPS isolation cabinets
Cloud platform & centralised supervision link the isolation power supply cabinets (IPS) through IoT gateways, with sensors and monitoring at each medical location. Acrel builds every layer — one supplier, one responsibility.
Key components

Isolating transformer

AITR decouples and limits leakage.

Insulation monitor

AIM — resistance · load · temp.

Fault locator

AIL — pinpoints the faulted branch.

Products — every component of a compliant system

Devices and tables, all to IEC 60364-7-710.
AITR isolating transformer

AITR Series — Medical Isolating Transformer

  • Single-phase IT supply; electrostatic screen; 2 × PT100.
  • IEC 60364-7-710 · IEC 61558-1 / -2-15.
Rated power
3.15–10 kVA
Insulation
≥ 400 MΩ
AIM-M10
AIM-M10
AIM-M300
AIM-M300
AIM-M300/SG
AIM-M300/SG
AIM-M Series — Insulation MonitoringM10M300M300/SG
Insulation resistance1–999 kΩ1–999 kΩ1–999 kΩ
Load current2–40 A5–40 A5–60 A
Temperature–20~+20 °C0~200 °C0~200 °C
SupplyAC 220 VDC 18–36 VDC 18–36 V
Interface7-seg · RS485RS485 · ModbusRS485 · int.
AID010
AID010
AID030
AID030
AID200
AID200
AID200-TP-40
AID200-TP-40
AID Series — Alarm & Display010030200200-TP-40
DisplayLEDDot-matrixDot-matrix4" touch
MonitoredAIM-M10AIM-M300AIM-M300AIM-M300
Max devices2161630
InterfaceRS485RS485RS485RS485
AIL100-4
AIL100-4
AIL150-8
AIL150-8
AIL160-6
AIL160-6
AIL Series — Insulation Fault Locator100-4150-8160-6
Channels486
Max circuits122448
Power supplyDC 18–36 VDC 18–36 VDC 18–36 V
InterfaceCAN, int.CAN, int.CAN, int.

Model data per latest Acrel brochure; verify the current datasheet before specifying.

HDR-60-24 power supply in the medical isolation cabinet

Medical Isolation Cabinet

  • Transformer · monitor · CT · power · alarm · breakers.
  • Optional AIL fault locator · dual feed · UPS.
Configuration
4 / 5 / 6-piece
Mounting
Floor / wall

Centralised monitoring — one overview for the whole hospital

Part of the Acrel EMS cloud platform; supervise every system from one interface.
Acrel centralised medical isolated power monitoring dashboard

Real-time monitoring

Data, status and fault alarms for each system.

Historical events

Recorded events and alarms for troubleshooting.

Insulation trends

Insulation data in curve form over time.

Fault statistics

Daily/monthly stats, rankings, unhandled events.

Standards & FAQ

StandardWhat it covers
IEC 60364-7-710Electrical installations in medical locations — Group 2 circuits.
IEC 61557-8Insulation monitoring devices for IT systems (AIM-M).
IEC 61557-9Insulation fault location systems (AIL).
IEC 61558-1 / -2-15Transformer safety; isolating transformers for medical locations (AITR).

Verify editions, local adoption and conformity documentation before specifying.

FAQ
An unearthed supply arrangement used in designated medical locations — an isolating transformer with insulation monitoring, plus alarms selected for the application.
It reports insulation resistance, so staff can identify deterioration or faults before they become critical.
IEC 60364-7-710 (installations), IEC 61557-8 (monitoring), IEC 61557-9 (fault location). Verify for your installation.
Yes. The Acrel Medical Isolated Power Monitoring System supervises many systems — status, alarms, events and trends.
Why Acrel

One supplier

Transformer to software.

Compliance-ready

IEC-aligned, tests on request.

Custom

Kits + cabinets to SLD.

Support

Docs & engineering.

Discuss your medical electrical project with Acrel

Get the right combination of transformer, monitoring, fault location and software — with datasheets and certification documents for your audit.

Acrel Co., Ltd. · No.253 Yu Lv Road, Jiading District, Shanghai 201801, China· 300286.SZ
Acrel · Medical IT
Acrel · Medical IT
IEC 60364-7-710CE Certified
Patient safety · Continuity of care

Medical Isolated Power Supply Systems for Hospitals — Monitoring, fault detection & IEC standards

A medical IT system isolates the supply and monitors insulation in operating theatres, ICU and emergency areas — so faults are found before they interrupt care.

3.15–10 kVA
Isolating transformer (AITR)
1–999 kΩ
Insulation monitoring (AIM)
up to 48
Fault-location circuits (AIL)
1 fault
Supply never interrupted

Why a medical IT system

Group 2 medical locations — continuity is a patient-safety matter.

A medical IT system is an unearthed distribution arrangement used in designated medical locations, combining an isolating transformer with insulation monitoring to keep power running after a first insulation fault and to limit leakage and touch current.

No interruption on first fault

Power stays on after an insulation fault; staff fix it on a planned schedule.

Leakage current limited

The isolating transformer keeps leakage and touch current within safe limits.

Fault found early

Monitoring + fault locator pinpoints the branch, so teams act on evidence.

System architecture

One continuous system, transformer to nurse station.
Acrel medical IT system architecture — cloud, gateway and IPS isolation cabinets
Cloud platform & centralised supervision link the isolation power supply cabinets (IPS) through IoT gateways, with sensors and monitoring at each medical location. Acrel builds every layer — one supplier, one responsibility.
Key components

Isolating transformer

AITR decouples and limits leakage.

Insulation monitor

AIM — resistance · load · temp.

Fault locator

AIL — pinpoints the faulted branch.

Products — every component of a compliant system

Devices and tables, all to IEC 60364-7-710.
AITR isolating transformer

AITR Series — Medical Isolating Transformer

  • Single-phase IT supply; electrostatic screen; 2 × PT100.
  • IEC 60364-7-710 · IEC 61558-1 / -2-15.
Rated power
3.15–10 kVA
Insulation
≥ 400 MΩ
AIM-M10
AIM-M10
AIM-M300
AIM-M300
AIM-M300/SG
AIM-M300/SG
AIM-M Series — Insulation MonitoringM10M300M300/SG
Insulation resistance1–999 kΩ1–999 kΩ1–999 kΩ
Load current2–40 A5–40 A5–60 A
Temperature–20~+20 °C0~200 °C0~200 °C
SupplyAC 220 VDC 18–36 VDC 18–36 V
Interface7-seg · RS485RS485 · ModbusRS485 · int.
AID010
AID010
AID030
AID030
AID200
AID200
AID200-TP-40
AID200-TP-40
AID Series — Alarm & Display010030200200-TP-40
DisplayLEDDot-matrixDot-matrix4" touch
MonitoredAIM-M10AIM-M300AIM-M300AIM-M300
Max devices2161630
InterfaceRS485RS485RS485RS485
AIL100-4
AIL100-4
AIL150-8
AIL150-8
AIL160-6
AIL160-6
AIL Series — Insulation Fault Locator100-4150-8160-6
Channels486
Max circuits122448
Power supplyDC 18–36 VDC 18–36 VDC 18–36 V
InterfaceCAN, int.CAN, int.CAN, int.

Model data per latest Acrel brochure; verify the current datasheet before specifying.

HDR-60-24 power supply in the medical isolation cabinet

Medical Isolation Cabinet

  • Transformer · monitor · CT · power · alarm · breakers.
  • Optional AIL fault locator · dual feed · UPS.
Configuration
4 / 5 / 6-piece
Mounting
Floor / wall

Centralised monitoring — one overview for the whole hospital

Part of the Acrel EMS cloud platform; supervise every system from one interface.
Acrel centralised medical isolated power monitoring dashboard

Real-time monitoring

Data, status and fault alarms for each system.

Historical events

Recorded events and alarms for troubleshooting.

Insulation trends

Insulation data in curve form over time.

Fault statistics

Daily/monthly stats, rankings, unhandled events.

Standards & FAQ

StandardWhat it covers
IEC 60364-7-710Electrical installations in medical locations — Group 2 circuits.
IEC 61557-8Insulation monitoring devices for IT systems (AIM-M).
IEC 61557-9Insulation fault location systems (AIL).
IEC 61558-1 / -2-15Transformer safety; isolating transformers for medical locations (AITR).

Verify editions, local adoption and conformity documentation before specifying.

FAQ
An unearthed supply arrangement used in designated medical locations — an isolating transformer with insulation monitoring, plus alarms selected for the application.
It reports insulation resistance, so staff can identify deterioration or faults before they become critical.
IEC 60364-7-710 (installations), IEC 61557-8 (monitoring), IEC 61557-9 (fault location). Verify for your installation.
Yes. The Acrel Medical Isolated Power Monitoring System supervises many systems — status, alarms, events and trends.
Why Acrel

One supplier

Transformer to software.

Compliance-ready

IEC-aligned, tests on request.

Custom

Kits + cabinets to SLD.

Support

Docs & engineering.

Discuss your medical electrical project with Acrel

Get the right combination of transformer, monitoring, fault location and software — with datasheets and certification documents for your audit.